Case Study · Data Centers

Remote power panels for a data-center operator in Mexico

Built for a data-center electrical contractor, for a data-center operator in Mexico

Aug 2026 – Dec 2026 an eight-figure program

Key facts

The build at a glance

816 RPPs on two orders

Units

Remote power panels with branch-circuit monitoring

Product

400A main circuit breaker, 42 circuits

Amperage

415Y/240V, 3-phase 4-wire

Voltage

Tin-plated copper

Bus

NEMA 1 (indoor)

Enclosure

35 kAIC main breaker, 25 kAIC branch breakers; 25 kA at the lowest-rated device

Interrupting rating

Siemens 3VA, 100%-rated LSI main

Breakers

The 768-panel order: two phases of 384, October–December 2026

Planned shipments

Jurupa Valley, California

Built in

01 · Challenge

The challenge

In Mexico, a data-center operator is bringing data-center capacity online in stages, and each stage’s installation needs its remote power panels on site. The first order from a data-center electrical contractor covered one stage with 48 panels. The second covered eight more stages with 768 panels at 415Y/240V, scheduled to ship in batches of about 70 as panels come off the line rather than held for one delivery.

02 · Build

What DEI built

Every panel is a 400A main-breaker, 42-circuit RPP at 415Y/240V, three-phase four-wire, in a NEMA 1 enclosure with tin-plated copper bus. Each carries a Siemens 3VA 400A LSI main, 100% rated at 35 kAIC, and fourteen 3-pole branch breakers rated 25 kAIC filling its 42 circuit positions. A branch-circuit monitoring system with split-core CTs on all 42 branch conductors and on the main reports current to a local display. The first order uses 60A branch breakers; the 768-panel order steps up to 100A.

QtyItemRatingVoltageEnclosureBusNotes
48Remote power panel400A MCB, 42 circuits415Y/240V 3Ø 4WNEMA 1Copper, tin-platedFourteen 60A 3-pole branch breakers; branch-circuit monitoring
768Remote power panel400A MCB, 42 circuits415Y/240V 3Ø 4WNEMA 1Copper, tin-platedFourteen 100A 3-pole branch breakers; branch-circuit monitoring

03 · Status

Where it stands

Done
Order
Done
Engineering
In progress · Sep 2026
Fabrication & bus bar
In progress · Sep 2026
Assembly
In progress · Sep 2026
QC
Expected ship Q4 2026
Shipped

Engineered, fabricated and assembled under one roof in Jurupa Valley, California.

As of September 2026 the 48-panel order is at the ready-to-ship stage, with shipment projected for October 2026, and the 768-panel order is in assembly. DEI’s delivery schedule splits the large order into two phases of 384 panels: the first window runs October–November 2026, the second November–December 2026. Completed panels are to ship as they come off the line, in planned batches of about 70, so installation does not wait for a whole phase.

Status as of September 2026, from DEI’s build records.

DEI’s manufacturing floor in Jurupa Valley, California
Photographed at DEI’s shop, Jurupa Valley, California.

04 · Specifications

Specifications, build by build

Order 1 of 2 — 48 RPPs with 60A branch breakers

From DEI’s submittal, Jul 2026

QtyItemRatingVoltageEnclosureBusNotes
48Remote power panel400A MCB, 42 circuits415Y/240V 3Ø 4WNEMA 1Copper, tin-platedFourteen 60A 3-pole branch breakers; branch-circuit monitoring
  • 400A 3-pole LSI main breaker, 100% rated, 35 kAIC (Siemens 3VA)
  • Fourteen 60A 3-pole branch breakers, 25 kAIC, each with trip-signal and auxiliary switches
  • Split-core CTs on all 42 branch conductors and the three main conductors, wired to a monitoring module and a local display
  • Main lugs for two sets of 250 kcmil per phase
  • 415Y/240V, 3-phase 4-wire; NEMA 1; tin-plated copper bus

From DEI’s submittal, Aug 2026

QtyItemRatingVoltageEnclosureBusNotes
768Remote power panel400A MCB, 42 circuits415Y/240V 3Ø 4WNEMA 1Copper, tin-platedFourteen 100A 3-pole branch breakers; branch-circuit monitoring
  • 400A 3-pole LSI main breaker, 100% rated, 35 kAIC (Siemens 3VA)
  • Fourteen 100A 3-pole branch breakers, 25 kAIC, each with trip-signal and auxiliary switches
  • Split-core CTs on all 42 branch conductors and the three main conductors, wired to a monitoring module and a local display
  • 415Y/240V, 3-phase 4-wire; NEMA 1; tin-plated copper bus
  • Delivery schedule: two phases of 384, to ship in batches of about 70 as panels complete

05 · Related

Related case studies

Send us your one-line diagram — we'll tell you what we'd build, and when.

Company names identify who DEI’s orders are for. Their use does not imply endorsement of DEI.

Dates, quantities and turnarounds as of September 2026, from DEI’s build and order records. Images are representative unless marked otherwise.