Case Study · EV & Fuel Retail

A 600A utility pull section for Rivian

Built for MC Electric, for Rivian

Sep 2026 – Oct 2026

Key facts

The build at a glance

One switchboard section

Units

Utility pull section with CT compartment

Product

600A, full-rated neutral

Amperage

480Y/277V, 3-phase 4-wire

Voltage

Tin-plated aluminum

Bus

NEMA 3R (outdoor)

Enclosure

65 kAIC

Interrupting rating

UL 891 low-voltage

Listing

Jurupa Valley, California

Built in

01 · Brief

The brief

In September 2026 MC Electric ordered one outdoor 600A switchboard section from DEI for Rivian: the utility pull section, which receives the serving utility’s service conductors and houses a CT compartment laid out to that utility’s requirements.

02 · Build

What DEI built

A 600A UL 891 low-voltage switchboard section at 480Y/277V, three-phase four-wire, 65 kAIC, in a NEMA 3R outdoor enclosure finished in ANSI 61 light gray. Its tin-plated aluminum bus carries 600A on each phase and the neutral and is braced for 65 kA RMS symmetrical. As the utility pull section it takes bottom conduit entry, keeps every termination reachable from the front, and houses the serving utility’s CT compartment and meter socket, laid out to that utility’s requirements.

QtyItemRatingVoltageEnclosureBusNotes
1Utility pull section with CT compartment600A480Y/277V 3Ø 4WNEMA 3RTin-plated aluminum65 kAIC; full-rated 600A neutral; CT compartment and meter socket laid out to the serving utility’s requirements; UL 891 low-voltage

03 · Status

Where it stands

Done
Order
In progress · Sep 2026
Engineering
Pending
Fabrication & bus bar
Pending
Assembly
Pending
QC
Expected ship Q4 2026
Shipped

Engineered, fabricated and assembled under one roof in Jurupa Valley, California.

As of September 2026 the pull section is in engineering: DEI’s submittal for approval is dated September 2026, and production is released once the customer approves it.

Status as of September 2026, from DEI’s build records.

DEI’s facility in Jurupa Valley, California
Photographed at DEI’s shop, Jurupa Valley, California.

04 · Specifications

Specifications, build by build

One order — 600A utility pull section

From DEI’s submittal, Sep 2026

QtyItemRatingVoltageEnclosureBusNotes
1Utility pull section with CT compartment600A480Y/277V 3Ø 4WNEMA 3RTin-plated aluminum65 kAIC; full-rated 600A neutral; CT compartment and meter socket laid out to the serving utility’s requirements; UL 891 low-voltage
  • UL 891 low-voltage switchboard section, 600A, 480Y/277V, 3-phase 4-wire, 65 kAIC
  • Tin-plated aluminum bus, 600A on each phase and the neutral, sized for a 65°C maximum temperature rise and braced for 65 kA RMS symmetrical
  • NEMA 3R outdoor enclosure in ANSI 61 light gray; bottom conduit entry; terminations accessible from the front
  • Utility pull section with a CT compartment and meter socket laid out to the serving utility’s requirements
  • Production is released on the customer’s approval of DEI’s submittal

05 · Related

Related case studies

Send us your one-line diagram — we'll tell you what we'd build, and when.

Company names identify who DEI’s orders are for. Their use does not imply endorsement of DEI.

Dates, quantities and turnarounds as of September 2026, from DEI’s build and order records. Images are representative unless marked otherwise.

About Us

Contact Us

Office Location

4725 Troy Ct.
Jurupa Valley CA 92509

Contact Info

Phone: +1 (866) 773-8050
Email: sales@deipower.com

The Importance of UL 891 Switchgear in Modern Facilities